Troubleshooting

Answers to common problems - the gateway won't start, a device won't connect, values look wrong, notifications don't arrive, and more.

The gateway won’t start

Run nexus check (Docker: nexusctl cli check). It tries everything the gateway needs, with the gateway’s own settings, and says which part fails:

MessageFix
PostgreSQL can’t be reachedStart the database, or correct DATABASE_URL in the settings file
TimescaleDB is installed but not loadedAdd timescaledb to shared_preload_libraries in postgresql.conf and restart PostgreSQL
QuestDB can’t be reachedStart QuestDB, or correct the QUESTDB_* settings
The port is in useAnother program has port 4000 or 4443; stop it or change PORT / NEXUS_HTTPS_PORT
An invalid settingThe message lists what is wrong in the settings file

On Windows, if setup finished but a database wasn’t ready, the service keeps retrying every minute: fix the problem and it starts on its own.

I can’t sign in

  • Forgot the administrator password: nexus admin reset-password admin@plant.com (Docker: nexusctl cli admin reset-password ...) prints a new one.
  • Locked out after wrong passwords: wait 15 minutes, or sign in from another computer.
  • “The password could not be checked”: no Active Directory / LDAP server answered. Check the servers in the provider’s settings and the network path to them.
  • Everyone was signed out: JWT_SECRET changed.

The browser warns about the certificate

The gateway starts with a self-signed certificate. Install one from your certificate authority under Connectivity → HTTPS (see Connectivity).

A device won’t connect

  1. Check the address and port, and that the gateway machine can reach the device (ping, or Test-NetConnection host -Port 502 on Windows).
  2. Check a firewall isn’t blocking the port between them.
  3. Modbus: check the unit ID. S7: check rack and slot, and allow PUT/GET in the PLC. Omron FINS over UDP: check the node numbers. OPC UA: check the endpoint URL.
  4. Serial ports: check the service may open the port (dialout on Linux, LocalSystem on Windows, the device passed through in Docker) and the baud rate, parity and stop bits.

Some tags are bad quality

Tag Explorer shows each bad tag’s reason:

  • Address rejected: the device doesn’t have that register or data block. Correct the address; other tags keep working.
  • Read timing out: the device is slow or overloaded. Increase the timeout, or move tags to a slower scan class.
  • Device offline: see A device won’t connect above.

Values look wrong

  • A float reads as a huge or tiny number: try another byte order, usually CDAB. See Devices.
  • Off by one register: Nexus addresses are one-based as in device manuals (40001 is the first holding register). If the manual counts from zero, add one.
  • Wrong engineering units: check the tag’s scaling.

An alarm didn’t notify anyone

Open the alarm in Alarms → Journal: its timeline lists every notification sent, and failed ones with the reason.

  • Email isn’t set up on this gateway: set the mail server under Connectivity → Email, then use Send test.
  • An SMTP error such as 535 Authentication failed: check the user name and password; Microsoft 365 and Gmail need SMTP AUTH or an app password.
  • Nobody on call: check the roster’s schedule and people’s Notification settings.

They use the gateway’s public address. Set it under System Health → This gateway to the address people and phones can reach, not localhost.

The camera scan button doesn’t work

Browsers only allow the camera on secure pages: the gateway needs HTTPS with a certificate the device trusts. See Barcode and QR scanning.

Operators don’t see my changes

Changes to views are part of the application’s draft. Publish the application (see Applications). Open screens switch to the new version within a minute.

A save in the view editor was refused

Someone else saved the view after you opened it. The editor says who and when; load their version, or save over it.

Writes are refused

  • “Read only” or no write control: your role lacks Operate, or the tag or its folder limits writes to other roles. See Tags.
  • 409 from the API or a banner in the app: you are on the standby gateway of a redundant pair. Use the active one.
  • Expression and query tags can never be written.

History has gaps

  • Check the tag has Historize on, and its history deadband isn’t too large.
  • If QuestDB was down, history was buffered on disk and is written when it comes back.
  • For edge gateways, history waiting to be sent shows on the link; it arrives when the link is back.

A script stopped

Open Scripting → Log. A script that loops for 5 seconds or runs out of memory is stopped, with the reason logged. System Health → Isolation and self-healing shows worker restarts.

Node-RED is in safe mode

A flow stopped Node-RED three times in two minutes. Open Automation, fix or disable the flow, and deploy.

Still stuck?

Raise the log level under System Health → This gateway, reproduce the problem, and look at the gateway’s log (see Operations). Then send the log, and the steps that cause the problem, to whoever supports your installation.