Getting started

Quick start

From an empty gateway to a live operator screen with an alarm and a trend in about fifteen minutes, using the built-in simulator.

This walk-through builds a small tank monitoring screen. It uses the built-in simulator, so you need no PLC. When the real equipment is connected later, you only change where the tags read from; screens, alarms and history keep working.

You need an account with the engineer or admin role.

1. Add a simulator device

  1. Open Devices in the sidebar and choose Add device.
  2. Name it sim and choose the protocol Simulator (built in - no PLC needed).
  3. Leave the scan rates as they are and save.

The device appears in the list as connected. A simulator makes values up inside the gateway: waves, random walks, counters, or memory that holds what you write.

2. Create tags

  1. Open Tag Explorer and choose New folder. Call it Tank101.

  2. Select the folder and choose New tag:

    • Name: Level, Tag type: device, Device: sim
    • Signal: sine, Min: 0, Max: 100, Period (s): 120
    • Units: %, and turn Historize on.
  3. Add a second tag, Setpoint, of tag type memory with the initial value 80 and units %.

  4. Add a third tag, HighLevel, of tag type expression, data type boolean, with the expression:

    {tank101.level} > {tank101.setpoint}

    Each tag’s Tag ID is made from its folder and name in lower case, so Tank101/Level is tank101.level. Use Insert tag reference to pick ids instead of typing them.

Select the folder: the values update live.

3. Build a view

  1. Open Views. The application bar at the top shows the default application, Operations.
  2. Choose New view, call it Tank 101, and open it.
  3. From the palette, drag a Tank onto the canvas. In the property panel on the right, set its tag to tank101.level.
  4. Drag a Setpoint control next to it and set its tag to tank101.setpoint. Operators can now type a new limit.
  5. Drag an Indicator, bind it to tank101.highlevel, and give it the caption High level.
  6. Save. Choose Open in viewer to try it: the tank fills and empties, and the indicator lights above the setpoint.

4. Publish it to operators

  1. In the application bar, open Settings and add a navigation item that opens the Tank 101 view. Make it the home view.
  2. Choose Publish, write a note such as First tank screen, and publish.
  3. Open /apps/operations in a new tab (or on a tablet). This is the full-screen client operators use.

Engineers’ changes stay in a draft until someone publishes them. See Applications.

5. Add an alarm

  1. Open Alarms → Rules and choose Add rule.
  2. Pick the tag tank101.level, type hi, setpoint 90, priority high, and save.
  3. Within two minutes the sine wave passes 90. The alarm appears in the ribbon at the top of the application and in Alarms → Journal.
  4. Acknowledge it from the ribbon or the journal, optionally with a note.

To get an email or text when it trips, set up email or SMS under Connectivity, then attach a notification route to the rule. See Notifications and on-call.

6. Look at the history

Open Trends, pick tank101.level, and choose a range such as 15m. Drag across the chart to zoom in, and use Export CSV to download what you see.

Where to go next